| Specification Parameter | Technical Details |
|---|---|
| Model | CC-E-G11 Triple IR Flame Detector |
| Key Measurements | Optical flame detection (Fire tracking) |
| Measurement Principle | Multi-spectrum optical sensing | Spectral range: IR 4-5um, UV 260nm | Triple-IR or Quad-IR/UV options available |
| Capacity Metrics | FOV (Field of View): 90° | Response time: 5-10S | Sensitivity metrics: 5 adjustable sensitivity levels | Operating environment: -40°C to 70°C, ≤95%RH (Non-condensing) |
| Enclosure Structure | Heavy-duty explosion-proof aluminum alloy casing with anti-corrosion paint finish coating | Explosion-proof class: Exd II CT6 / DIP A20 TA, T6 | Protection metrics: IP66 | Electrical interface: M20X1.5mm |
| Display Configuration | Base quotation is for standard optical blind version with operational current ≤30mA (Alarm state ≤45mA) |
| Alarm Method | Integrated 3-level alarm logic supporting sound & light indicators | High & low limits independently configurable per loop | Each loop binds up to 3 relay channels for synchronized linkage output |
| Mounting Hardware | Included heavy-duty adjustable multi-axis mounting bracket hardware kit |
| Output Signal | Simultaneous 3-mode output: 4-20mA analog loop, RS485 (Modbus-RTU) digital bus, and Relay output |
| Power Supply | 24 VDC (Working range: 18-30 VDC) |
| Tailored OEM/ODM Capability | Custom spectral configurations (3IR / 4IR / UV-IR matrices), customized relay linkage programming, specialized casing colors/logos, and tiered volume bidding pricing. |
| Industrial Applications | Oil & gas refineries, chemical processing plants, fuel storage tank areas, aircraft hangars, paint spraying booths, and high-risk industrial manufacturing warehouses. |