Chaosensor CC-E-G08 Multiparameter Air Quality Sensor

CC‑E‑G08 Multiparameter Air Quality Sensor outdoor multi‑gas environmental monitoring sensor
Specification Parameter Technical Details
Model CC-E-G08 Multiparameter Air Quality Sensor
Measurement Principle Multi-sensor fusion premium core combining electrochemical, laser scattering, NDIR, and PID technology
Combustible & Base Gases Matrix
Ex (Combustible Gas)0-100% LEL | Accuracy: ≤±1%~3% F.S. | Res: 0.1% LEL | T90 ≤10s
O₂ (Oxygen)0-30% Vol / 0-100% Vol | Accuracy: ≤±1%~3% F.S. | Res: 0.01% Vol / 0.1% Vol | T90 ≤10s
CO₂ (Carbon Dioxide)0-5000ppm / 20% Vol / 100% Vol | Accuracy: ≤±1%~3% F.S. | Res: 1ppm / 0.01% Vol | T90 ≤20s
CH₄ (Methane)0-100% LEL / 0-100% Vol | Accuracy: ≤±1%~3% F.S. | Res: 0.1% LEL / 0.01% Vol | T90 ≤10s
Common Toxic & Industrial Gases Matrix
CO (Carbon Monoxide)0-100ppm / 1000ppm / 2000ppm / 5000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.1ppm / 1ppm | T90 ≤25s
H₂S (Hydrogen Sulfide)0-50ppm / 100ppm / 2000ppm / 10000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm / 0.1ppm / 1ppm | T90 ≤30s
SO₂ (Sulfur Dioxide)0-20ppm / 100ppm / 2000ppm / 10000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm / 0.1ppm / 1ppm | T90 ≤30s
NO (Nitric Oxide)0-100ppm / 2000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm / 0.1ppm | T90 ≤30s
NO₂ (Nitrogen Dioxide)0-20ppm / 100ppm / 2000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm / 0.1ppm | T90 ≤25s
O₃ (Ozone)0-5ppm / 20ppm / 100ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.001ppm / 0.01ppm | T90 ≤20s
NH₃ (Ammonia)0-50ppm / 100ppm / 5000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm / 0.1ppm / 1ppm | T90 ≤30s
Cl₂ (Chlorine)0-20ppm / 100ppm / 2000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm / 0.1ppm | T90 ≤30s
HCl (Hydrogen Chloride)0-20ppm / 100ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm / 0.1ppm | T90 ≤30s
HCN (Hydrogen Cyanide)0-30ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm | T90 ≤30s
HF (Hydrogen Fluoride)0-10ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm | T90 ≤30s
PH₃ (Phosphine)0-5ppm / 2000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.001ppm / 0.1ppm | T90 ≤30s
F₂ (Fluorine)0-1ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.001ppm | T90 ≤30s
ClO₂ (Chlorine Dioxide)0-1ppm / 100ppm / 200ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.001ppm / 0.01ppm / 0.1ppm | T90 ≤30s
VOCs & Organic Chemicals Matrix
TVOC / VOC / PID (Photoionization)0-10ppm / 100ppm / 2000ppm / 20000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.001ppm / 0.01ppm / 0.1ppm / 1ppm | T90 ≤30s
HCHO (Formaldehyde)0-10ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.001ppm | T90 ≤30s
C₂H₄ (Ethylene)0-10ppm / 100ppm / 1000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm / 0.1ppm / 1ppm | T90 ≤50s
C₂H₄O (Ethylene Oxide)0-20ppm / 100ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm / 0.1ppm | T90 ≤30s
C₆H₆ (Benzene)0-10ppm / 100ppm / 2000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm / 0.1ppm / 1ppm | T90 ≤30s
C₇H₈ (Toluene)0-2000ppm | Accuracy: ≤±1%~3% F.S. | Res: 1ppm | T90 ≤30s
C₈H₁₀ (Xylene)0-100ppm / 2000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.1ppm / 1ppm | T90 ≤30s
CH₃Br (Methyl Bromide)0-100ppm / 2000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm / 1ppm | T90 ≤30s
CH₃I (Methyl Iodide)0-100ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm | T90 ≤30s
Specialty & Rare Gases Matrix
COCl₂ (Phosgene)0-1ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.001ppm | T90 ≤30s
SiH₄ (Silane)0-50ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm | T90 ≤30s
AsH₃ (Arsine)0-1ppm / 10ppm / 50ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.001ppm / 0.01ppm | T90 ≤30s
GeH₄ (Germane)0-2ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.001ppm | T90 ≤30s
B₂H₆ (Diborane)0-10ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm | T90 ≤30s
N₂H₄ (Hydrazine)0-10ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm | T90 ≤30s
THT (Tetrahydrothiophene)0-100mg/m³ | Accuracy: ≤±1%~3% F.S. | Res: 0.1mg/m³ | T90 ≤60s
Br₂ (Bromine)0-100ppm / 2000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm / 1ppm | T90 ≤30s
I₂ (Iodine)0-10ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm | T90 ≤30s
C₄H₆O₂ (Vinyl Acetate)0-100ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.01ppm | T90 ≤30s
SO₂F₂ (Sulfuryl Fluoride)0-100ppm / 5000ppm | Accuracy: ≤±1%~3% F.S. | Res: 0.1ppm / 1ppm | T90 ≤30s
CH₃SH (Methyl Mercaptan)0-200mg/m³ | Accuracy: ≤±1%~3% F.S. | Res: 0.1mg/m³ | T90 ≤30s
He (Helium)0-100% Vol | Accuracy: ≤±1%~3% F.S. | Res: 0.01% Vol | T90 ≤20s
Ar (Argon)0-100% Vol | Accuracy: ≤±1%~3% F.S. | Res: 0.01% Vol | T90 ≤20s
Xe (Xenon)0-100% Vol | Accuracy: ≤±1%~3% F.S. | Res: 0.01% Vol | T90 ≤20s
Hardware & Structural Specifications
Capacity Metrics Highly customizable arbitrary combination factor tailored per project | Simultaneous multi-channel continuous capture
Enclosure Structure Heavy-duty enhanced outdoor radiation shield (aspiration / multi-plate louvers) casing for ultimate weather protection
Mounting Hardware Included heavy-duty stainless steel U-bolt pole brackets kit
Output Signal RS485 (Modbus-RTU)
Power Supply 12 – 24 VDC
Tailored OEM/ODM Capability Custom parameter combinations, bespoke Technical Matrix setup, private-label laser-engraved branding, and targeted volume pricing brackets.
Industrial Applications Smart city environmental monitoring grids, industrial estate ambient air quality networks, roadside traffic emissions tracking, seaport acoustic & gas assessment, and comprehensive meteorological monitoring stations.
To request the complete PDF technical specifications, please submit your inquiry below.

CC‑E‑G08 Multiparameter Air Quality Sensor

The CC‑E‑G08 Multiparameter Air Quality Sensor is a fully configurable outdoor multi‑gas monitoring unit built on multi‑sensor‑fusion technology including electrochemical, laser scattering, NDIR and PID principles. This CC‑E‑G08 Multiparameter Air Quality Sensor supports arbitrary custom gas‑matrix combinations, covering combustible gas, oxygen, CO₂, toxic industrial gases, VOCs, formaldehyde and specialty rare gases. The CC‑E‑G08 Multiparameter Air Quality Sensor delivers fast T90 response time and accuracy within ±1‑3% full‑scale for selected gas channels. Protected by heavy‑duty enhanced multi‑plate louver solar‑radiation‑shield enclosure, the CC‑E‑G08 Multiparameter Air Quality Sensor maintains stable performance under harsh outdoor climate conditions.

The CC‑E‑G08 Multiparameter Air Quality Sensor transmits all multi‑channel measurement data via RS485 Modbus‑RTU interface for seamless connection with data loggers and SCADA platforms. It operates on standard 12‑24 VDC power supply and comes complete with heavy‑duty stainless‑steel U‑bolt pole‑mounting hardware. The CC‑E‑G08 Multiparameter Air Quality Sensor offers comprehensive OEM and ODM services, including bespoke gas‑matrix setup, private‑label laser‑engraved branding and volume‑based pricing tailored for project‑bidding requirements.

For industrial parks, seaports and outdoor smart‑city environmental grids, fixed single‑gas monitors cannot meet complex multi‑component ambient‑air assessment requirements. The CC‑E‑G08 Multiparameter Air Quality Sensor lets integrators pick only required gas channels without paying for redundant sensing modules. Whether deployed for roadside emission tracking, industrial‑estate air‑quality networks or comprehensive meteorological stations, the CC‑E‑G08 Multiparameter Air Quality Sensor provides continuous, traceable multi‑gas outdoor measurement outputs.

Typical Applications

  • Smart‑city outdoor environmental‑monitoring sensor grids
  • Industrial‑park multi‑component ambient‑air‑quality networks
  • Roadside traffic‑related emission‑effect tracking
  • Seaport multi‑gas ambient‑condition assessment
  • Professional comprehensive meteorological‑station gas‑monitoring

Frequently Asked Questions

What is multi‑sensor‑fusion gas‑detection?

Multi‑sensor‑fusion combines different sensing cores such as electrochemical, NDIR infrared, PID photoionization and laser‑scattering. Each technology matches specific gas types to balance response speed, resolution and long‑term stability for complex mixed‑gas environments.

Core Advantages & Product Selection Guide

The CC‑E‑G08 Multiparameter Air Quality Sensor provides project‑oriented flexible gas‑channel configuration for outdoor complex‑gas‑scenario monitoring. If you need multi‑gas monitoring for offices, schools and building indoor environments, choose our indoor‑type CC‑E‑G09 Indoor Air Quality Sensor. Browse the full environmental‑instrument portfolio at the environmental smart‑city sensors page.

This field is required.
This field is required.
This field is required.
This field is required.
This field is required.